What FANUC Alarm 607 Actually Means
Reading the alarm text: n AXIS: CNV. SINGLE PHASE FAILURE
FANUC's αi series servo amplifier descriptions (B-65282EN) have a separate status code set for each module. The prefix tells you what the module is: CNV is the converter (input, rectifier, DC link); INV is the inverter (motor feed); SV is axis control. As 607 has CNV it's the converter so no axis control or motor output.
PSM vs PSMR: why 607 and 613 look identical
613 has the same message and the same diagnostic path. On machines with more than one power module the two will usually be present together so don't go to any great lengths to decide which module has which number. Just measure the input.
The fastest 30 second triage: how many axes are alarming?
Count the axes prior to opening the cabinet. The axis number is just a display convention rather than a physical location. A single open phase will indicate every axis that the module feeds. A single axis will point to that axis' path or module; multiple axes will point to the common AC input (which is normally the incoming supply fault).
Why Alarm 607 Happens: Six Root Causes
Six faults give 607. Five of them are external to the module.
1. A genuine open phase on the incoming supply
Blown fuse, one breaker pole tripped, a broken cable core and a phase lost upstream. Field signature is that the other machines on the circuit go all to pot after a power cut.
2. Loose, oxidized or burnt terminals at the PSM input
L1, L2 and L3 land on screws that loosen, crimp badly or oxidise. Field signature is blackened terminals, carbonised insulation and a screw you can turn by hand.
3. Main contactor not making all three phases
Pitted contacts, a weak coil or a contactor that pulls in and then drops out. Field signature is chatter at power up and an alarm that comes and goes.
4. Transformer tap or voltage-class mismatch
Wrong transformer tap (200v module on a 400v supply (or the other way round), undersized transformer). Field signature is alarms post move/retrofit, only under load.
5. Damaged input cable, reactor or filter
Cable wear in a drag chain, or an inter-turn short in the reactor or filter. Field signature is that the alarm follows a mechanical action (the cable is pulled, the axis moves).
6. PSM internal fault — a "false" 607
The input detection circuit, rectifier or an old DC link capacitor has failed and the module is reporting a phase that is not actually missing. Field signature is three phases balanced, terminals clean, another circuit tried, alarm at power up. That's the only reason you'd open the module.
What alarm 607 is not
A servo motor, an encoder, a jammed axis, a parameter or a program can't give you 607. Nothing is on the converter input path. If your suspect list has any of those then you're on the wrong side of the DC link.
Safety First: Before You Open the Cabinet
Stop before you measure. The DC link is still live after the main breaker has been switched off. Prove it's dead with a meter reading close to 0v, not just by the passage of time. Qualified personnel, one hand, correct PPE, lock-out/tag-out.
Capture the alarm screen and the PSM display digits prior to power being lost.
Step-by-Step Diagnosis
Eight steps, from least to most invasive.
- Photograph the screen and the PSM display. 401 (VRDY OFF) next to 607 points to the module and multiple axes at the same time indicates the input side. Note whether the alarm occurs at power up or under load.
- Confirm which module's display you're looking at. Each module has its own code set. A digit on a servo amp means one thing on a PSM and another thing on a different module.
- Measure the three line voltages at the PSM input (AC volts, 600v or higher: L1–L2, L2–L3, L3–L1). They should be very close to each other and within the rated input (200—220v on a 200v class unit as per the rating plate, 200-220v on a 400v class unit). If a pair are at zero then you have an open phase.
- Check every fuse pole, every breaker pole and every terminal. One blown fuse, one tripped pole or one blackened terminal is your root cause.
- Check the main contactor. Watch it pull in, measure across each contact, check coil voltage. Chatter or a missing phase means it's time for a replacement.
- Check the transformer tap and voltage class. If the tap is wrong or the transformer is undersized it has to be sorted out before any other judgement can be made.
- Re-measure under load (i.e. whilst the spindle is accelerating or taking a heavy cut). A phase which is stable at idle and collapses under load indicates a high resistance joint or insufficient supply capacity. That's the classic case of a machine passing a no load test and then failing in production.
- Input clean, 607 persisting? A swap test with a known good unit will resolve that.
The eight steps at a glance
| Step | Measure | Ends the search |
|---|---|---|
| 1 | Alarm screen, PSM | Multi-axis, or 401 |
| 2 | Module identity | Code matched to module |
| 3 | L1–L2, L2–L3, L3–L1 | One pair low |
| 4 | Fuses, breakers, terminals | Blown pole |
| 5 | Contactor | Chatter, missing phase |
| 6 | Tap, rating plate | Wrong tap or undersized |
| 7 | Same pairs under load | Phase drops under load |
| 8 | Known-good module | Fault follows it |
No known good module? We'll send you load tested exchange PSMs and bench test yours. See the load testing and verification.
How to Tell Whether the PSM Itself Is Bad
Three findings justify the condemnation of the module; the second of these is easily overlooked.
Three findings that point to the module
Line voltages balanced and within rating when re-measured under load. The alarm pattern follows the module rather than the supply. It appears at power-up or as soon as the machine loads and persists on a change of supply circuit. The associated alarms (401 VRDY OFF and 613) will normally be with it.
What you can safely rule out
Correct readings at the input clear everything downstream of the DC link completely and the motor stays where it is. That prevents the most expensive wrong purchase of all.
Swap test: the fastest confirmation
A known good module of the same family will sort it out on power up. Match the family exactly (use the part number from the rating plate). We stock both new and used FANUC power supply modules (PSM/PSMR), all of which are tested prior to despatch.
Repair or Replace? A Decision Table
Match the symptom to the row, act on the third column.
| Symptom | Most likely cause | Action |
|---|---|---|
| Alarm at power-up, phases normal | PSM internals: detection circuit, rectifier, DC link capacitor | Repair or exchange the module |
| Only under acceleration or heavy cutting | Supply capacity, voltage drop under load | Fix the supply: transformer capacity, cable size, dedicated circuit |
| Started after a move or retrofit | Wiring, terminals, transformer tap | Re-terminate, verify the tap, re-measure |
| Intermittent, in step with other machines | Phase imbalance, utility fluctuation | Add phase-failure and phase-sequence protection |
| Still alarming after a swap | Upstream circuit not repaired | Return to step 3 and measure again |
| Several axes with 607 and 613 | Shared input side | Check the supply and contactor, leave the module alone |
Repair or replace: what actually decides it
Downtime and stock are the deciding factors. Repair is quicker when the fault is in the input detection or rectifier stage. Exchange is the winner if you have a matching unit in stock.
We do component level repair on FANUC PSMs and have tested exchange units for the A06B-6110 and A06B-6140 families. Just send us the part number and an alarm photo via the FANUC servo amplifier and PSM repair and we'll let you know which route is the quickest.
The Last
Measure the input before you jump to any conclusions regarding the module. If the input readings are valid under load then it's a module problem and that's what will determine what you end up buying.
Want a second opinion? Send the alarm photo and the PSM part number, and our technicians will tell you what to measure. Contact SongWei CNC now!