24/7 Emergency Service

+86 167 3023 1836

Contact us Now!

admin@songweicnc.com

EN

How to solve FANUC Alarm 432?

NOV. 19, 2026

FANUC Alarm 432 is a converter voltage alarm (commonly displayed as CNV. LOWVOLT CON./POWFAULT or CNV. LOW VOLT CONTROL depending on the CNC).

It indicates that the converter control power supply voltage has dropped. On some of the older FANUC machines it can also indicate a missing input power phase in the Power Supply Module (PSM).

How to solve FANUC Alarm 432?

Possible causes are low input voltage, an unstable control power supply, missing input phases, poor electrical connections or a fault within the power module itself. The correct procedure for diagnosis will of course depend on the particular FANUC power supply and amplifier model in question.

What does FANUC Alarm 432 mean?

FANUC Alarm 432 is a voltage problem in the converter section of the servo power system.

The exact meaning varies between FANUC control generations and module configurations:

FANUC system or module Alarm 432 meaning
Series 16i/18i Model A – PSM Missing input power phase
Series 16i/18i Model A – PSMR Control power supply voltage drop
Series 16i/18i Model A – α-series SVU Control power supply voltage drop
Series 0i Model C – PSM / PSMR / β-series SVU Control power supply voltage drop
βi SVPM Converter control power supply undervoltage

For certain βi amplifier configurations the alarm may be accompanied by a module status code. The FANUC βi SVPM maintenance manual is an example of this with CNC Alarm 432 mapped to STATUS1 code b1 which is a reduced control power supply voltage.

Always identify the CNC generation and module model prior to following any troubleshooting procedure.

Common Causes of FANUC Alarm 432

The main possible causes include:

1. Low Input Power Supply Voltage

An inadequate or unstable incoming power supply will prevent the converter control circuit from getting the voltage it needs.

Check that the input voltage is within the specification for the FANUC module in question. For the applicable 3 phase systems, check that all 3 input phases are present.

2. Missing Input Power Phase

On certain older FANUC PSM's Alarm 432 will specifically indicate a missing input power phase.

A power supply phase can be interrupted as a result of a defective cable, a loose terminal or a problem with the supply upstream.

This cause should only be applied to systems whose manuals define Alarm 432 as phase loss.

3. Low 24V Control Power Supply

Some FANUC beta i servo amplifier configurations use an external 24VDC control power supply. If that voltage should drop below the required level the amplifier will report a converter control power undervoltage alarm.

4. Poor Power Connections

Loose connectors, damaged cables and poor electrical contact can all interrupt the control power supply and lead to voltage related alarms.

5. Internal Power Supply Module Failure

If the incoming power, control voltage and the connections are all fine but Alarm 432 is still persisting then an internal fault in the PSM, PSMR or servo amplifier will likely need further investigation.

How to Troubleshoot FANUC Alarm 432 Step by Step

Step 1: Confirm the Alarm and Identify the Module

Firstly confirm the full alarm message as displayed on the CNC screen.

Record the FANUC CNC model and note the power supply or servo module that is fitted (e.g. PSM, PSMR, SVU, SVM or SVPM).

Also check the module's LED or STATUS display for any further diagnostic info as this will tell you which of the voltage supplies is the problem.

Step 2: Check the Incoming Power Supply

Measure the input voltage in accordance with the electrical specifications of the module in question.

For systems requiring 3 phase input power, make sure all phases are present and that the voltage is within the required range.

If the voltage is bad or one phase is missing then check the supply upstream of it, the circuit breakers, the contactors and the electrical connections.

Step 3: Check the External 24V Control Power Supply

For the applicable FANUC βi SVM configurations, check the external 24VDC control power supply.

The FANUC βi maintenance manual specifies a normal control supply of 24VDC +/-10% with a minimum normal voltage of 21.6V for the covered configuration.

If the voltage's too low then check the power supply and its cabling first before thinking about an amplifier fault.

Step 4: Inspect the Connectors and Cables

Check the power supply and control circuit connections for loose terminals, damaged cables and poor contact.

For the βi SVM configurations covered by the FANUC manual B-65325EN/01, CXA19A and CXA19B are specifically called out as inspection points.

Always refer to the wiring diagram for the exact module prior to disconnecting or testing any connectors.

Step 5: Evaluate the Power Supply Module

If the input voltage and control power supply are both OK then further testing of the power supply or servo amplifier may be required.

Depending on the module this may be the PSM, the PSMR or the SVM internal power supply circuits.

Use the diagnostic procedures in the relevant FANUC maintenance manual to determine whether the module is faulty. Don't just replace the whole unit on the basis of Alarm 432.

Step 6: Restore Power and Verify the Result

Once you've sorted out the voltage or the connection issue, restore power in accordance with the machine manufacturer's instructions.

Check the module status display and the CNC alarm screen to confirm that the voltage condition has returned to normal and that Alarm 432 has not reappeared.

Difference Between FANUC Alarms 432, 433, and 434

These three alarms are all to do with different voltage conditions in the servo power system.

Alarm Meaning
432 Converter control power supply undervoltage
433 Converter DC link undervoltage
434 Inverter control power supply undervoltage

Although the alarms are power supply related they are in fact related to different circuits and will require different diagnostic procedures. Always check the exact alarm description in the manual for your particular FANUC system.

Common Mistakes When Fixing FANUC Alarm 432

Avoid these common troubleshooting mistakes:

  • Assuming that every Alarm 432 means phase loss: that's dependent on the FANUC system and the power module.
  • Ignoring the control power supply: checking just the main input voltage may well have missed a low 24VDC control supply.
  • Don't replace the PSM too early. Check the incoming power and the electrical connections first.
  • Alarm 432 was being confused with Alarm 433. Converter control power undervoltage and DC link undervoltage are two different faults.

A proper diagnosis has to start with module identification and actual voltage measurements.

Safety Precautions During Troubleshooting

Power supply and servo amplifier modules contain hazardous voltages. Prior to disconnecting any cables or replacing any components, you must follow the machine manufacturer's shutdown and electrical isolation procedures.

Residual voltage may remain in the amplifier even after the main power has been switched off. Note the discharge waiting time as specified in the relevant FANUC manual.

Three phase voltage measurements and internal electrical testing should be carried out only by a qualified technician using the appropriate equipment.

Should you repair or replace the FANUC power supply module?

The decision on Alarm 432 will be based on the actual root cause.

If the fault is due to an unstable input supply, missing phase or a faulty external control power supply then rectifying the external electrical condition will eliminate the alarm without the need to replace the module.

If the PSM, PSMR or servo amplifier has an internal fault then professional testing can establish whether it is repairable.

When you need to replace it, make sure you have the full part number, the correct electrical specs and that it's actually compatible with the FANUC system you're using. If it's a used module then you'll also need to check its test status and warranty.

How SongWei CNC Can Help

SongWei CNC supply new and used FANUC CNC spare parts. This includes Power Supply Modules (PSM), Regenerative Power Supply Modules (PSMR), servo amplifiers, spindle amplifiers, motors and CNC circuit boards.

We also offer testing and repair of FANUC items.

If you need help with FANUC Alarm 432 then please provide your CNC model, complete power module part number, the alarm info and a photo of the status display on the module. That will enable us to understand the fault and determine what parts we need to replace or what repair is required.

Conclusion

FANUC Alarm 432 is a converter power supply voltage fault. It could be due to a missing input phase or a drop in the control power supply voltage (depending on the system).

First, identify the installed module, then check the incoming voltage, control power supply, and electrical connections. If these checks do not resolve the issue, investigate the internal power supply module.

Accurate diagnosis before replacing components can help reduce unnecessary repair costs and machine downtime.

Related Product Types

If you found this article interesting, you may want to know more about these related product types. 

Contact Us to Maximize Your Profit

Enter part information below to check price and availability.

Usually ship by UPS or DHL with delivery around 3 working days.

All parts are tested OK before shipping out with a 12-month warranty.

Provide technology guidance service upon receiving the part.

CONTACT US
Thank you! Your message has been sent.
Unable to send your message. Please fix errors then try again.

Search